PVe Troubleshooting

The most common misfunctions and defects

Causes of reduced performance & lower yield of PV generators

Recognizable by
measurement of match losses
Possible cause / remedy
planning errors / reconfiguration
Recognizable by
Power fed in is too low for the location and power of the generator
Possible cause / remedy
Planning errors / reconfiguration, replacement of inverters
Recognizable by
I-U characteristic curve has "bumps", peak power too low, optical check
Possible cause / remedy
Obstacle in the immediate vicinity of the module (e.g. bird droppings) / Remove obstacle
Recognizable by
I-V characteristic curve is "dented", peak power too low
Possible cause / remedy
Obstacle at some distance (high diffuse light component) / remove obstacle

Recognizable by

Internal series resistance Rs too high

Possible cause / remedy

Material, planning, assembly errors / Cleaning, replacement
Recognizable by
I-V characteristic curve is "dented", peak power too low
Possible cause / remedy
Material, manufacturing defects / exchange
Recognizable by
I-V characteristic curve is "dented", peak power too low
Possible cause / remedy
Material defects / replacement by supplier
Recognizable by
Optical control, peak power too low (see also diffuse shading)
Possible cause / remedy
Material defects / replacement by supplier
Recognizable by
Optical control, peak power too low (see also diffuse shading)
Possible cause / remedy
Material defects / replacement by supplier
Recognizable by
Optical inspection
Possible cause / remedy
Material, manufacturing defects / replacement by suppliers
Recognizable by
I-V characteristic curve is "dented", peak power too low
Possible cause / remedy
Material, manufacturing defects / replacement by suppliers
Recognizable by
Visual inspection, such as diffuse shading
Possible cause / remedy
High dust load (usually not a problem in Germany). Check modules regularly / clean
Recognizable by
I-V characteristic curve has "bumps", peak power too low, visual inspection
Possible cause / remedy
Depending on region and location normal / Cleaning
Recognizable by
Optical inspection
Possible cause / remedy
Hail damage, assembly error, transport damage / replacement by supplier
Recognizable by
Peak power too low, series internal resistance Rs higher than calculated
Possible cause / remedy
Soldering errors, material defects, corrosion / Replacement by supplier
Recognizable by
Peak power of the string reduced by module power
Possible cause / remedy
Overload, material defect / repair
Recognizable by
Peak power of the string reduced by module power
Possible cause / remedy
Assembly error / repair
Recognizable by
Shading a module can dramatically reduce the performance of the string
Possible cause / remedy
Planning, assembly errors / repairs
Recognizable by
Internal series resistance Rs too high
Possible cause / remedy
Planning errors / replacement of the cabling
Recognizable by
Internal series resistance Rs too high
Possible cause / remedy
Assembly error / repair
Recognizable by
Internal series resistance Rs too high
Possible cause / remedy
Assembly error / repair
Recognizable by
Internal series resistance Rs too high
Possible cause / remedy
Assembly errors / cleaning, repair
Recognizable by
Peak power of the system too low
Possible cause / remedy
Planning and assembly errors (match losses) / reassembly of modules after peak power measurement
Recognizable by
Peak power of the module too low
Possible cause / remedy
Manufacturing defects / price reduction, replacement by supplier
Recognizable by
Peak power of the system too low, Open circuit voltage Uoc too low, Characteristic curve
Possible cause / remedy
Manufacturing defects / replacement by supplier
Recognizable by
Peak power too low, characteristic curve
Possible cause / remedy
Manufacturing defects / price reduction, replacement by supplier
Recognizable by
Peak power too low, voltage too low, characteristic curve
Possible cause / remedy
Planning errors, material defects / repair, replacement
en_US